Technical Design
The whole datacenter infrastructure is Uptime Institute conform, Level Tier III.
The entire infrastructure is UI TIER III compliant
Power Distribution Key Facts
Main Power Connection direct from local mid-voltage 150kV substation with own transformer owned by the data center
Redundant back-up power supply via 2 generators 2 x 800 kVA with at least 72 hours autonomy
Redundant UPS systems to the racks with 2 x 300kW and 5min bridging time via batteries
Redundant main power distribution and power sub-distribution
Residual power monitoring
Over-voltage protection
Technical design to deliver 300kW available IT load in each IT room
Lightning protection system class I according to EN 62305
Full monitoring solution
Cooling Distribution Key Facts
Redundant cold production over 2 chiller sets with each 350kW
Redundant cold distribution over 4 air handling units each 100kW
Fully redundant piping design
Technical design to deliver 300kW available IT load in each IT room
Implementation of CO2 neutral refrigereant
Full monitoring solution
Connectivity
Separate, redundant Meet-Me rooms for telecom & connectivity providers
Density
3 - 12 kw per rack
total 300kW available IT load per IT room